DKRCC.PD.AB0.A3.02 / 520H5227
MAKING MODERN LIVING POSSIBLE
The TE series expansion valve regulate the injection of refrigerant into evaporators. It controls the refrigerant flow based on the superheat. The exchangeable power element is produced with the well known Danfoss laser welding technology for extended lifetime capability. The TE series is available with a wide range of orifices which will cover a wide range
of applications.
Technical brochure
Thermostatic expansion valves type TE5 to TE55
Features Large operating range: N-range -40°C to +10°C / B-range -60°C to -25°C
Interchangeable orifice assembly.
Stainless steel power element, capillary tube and bulb.
Wide capacity range. MOP function is available.
Superior charge performance. Patented bulb strap design.
MWP (maximum working pressure) 28 bar. Wide capacity range to minimize capacity gap and overlap.
TE55 has balanced orifice design.
2 DKRCC.PD.AB0.A3.02 / 520H5227
Danfoss A/S (AC-SMC / sw), 03 - 2011
Identification
Element label
Orifice assembly marking
for TE5 to TE55
The thermostatic element is fitted with a label (on top of the diaphragm). The code refers to the refrigerant for which the valve is designed:X = R22N = R134a
S = R404A/R507Z = R407C
The label holds information like valve type, evaporating temperature range, MOP point, refrigerant, and max. test pressure, PS.Orifice assembly for TE5, TE12, 20 and 55
The orifice assembly is marked on top of the spring cup, e.g. as shown in the figure.For a given size of valve, the same orifice
assembly can be used for valves with ranges N and B.
TE12 = For valve type 05 = Orifice no.
067B2708 = Orifice code no. for sales order 1009 = Production date (Week, Year)
Capillary tube tag for TE5 to TE55
The label gives the orifice size (04). A new label always accompanies a new orifice assembly.
TE5 to TE55
Max. temperature
Bulb, when valve is assembled: 100°C
Complete valve when not assembled: 70°C
SS = static superheat OS = opening superheat
SH = SS + OS = total superheat Q nom = rated capacity
Q max = maximum capacity
Static superheat SS can be adjusted with setting spindle.
The standard factory superheat setting SS is 4 K.The opening superheat OS is 4 K from when opening begins to where the valve reaches its rated capacity Q nom .
Superheat
Example
Static superheat SS = 4 K Opening superheat OS = 4 K Total superheat SH = 4 + 4 = 8 K
Using orifice with range B element, please check superheat under running conditions and re-adjust superheat setting, if necessary.
Min. temperature: –60°C Max. test pressure: 32 bar
Maximum working pressure:
28 bar
Technical data
021导弹艇Danfoss A/S (AC-SMC / sw), 03 - 2011 DKRCC.PD.AB0.A3.02 / 520H5227
黑
止血钳3
Design/Function
General
All TE valves have an interchangeable orifice assembly.
TE5 to TE55 valves are built up of three main components:
1 - Thermostatic element
2 - Orifice assembly
3 - Valve body with connections
The orifice is refrigerant and range independend.
All valves are equipped with external pressure equalization.
To ensure long operating life, the valve cone and seat are made of a special alloy with particularly good wear properties.
1. Thermostatic element (diaphragm)
ceb文件2. Interchangeable orifice assembly
3. Valve body
4. Superheat setting spindle (see instructions)
5. Ext. pressure equalizing connection with 1⁄4 in./6 mm flare nut
4 DKRCC.PD.AB0.A3.02 / 520H5227
Danfoss A/S (AC-SMC / sw), 03 - 2011
Ordering
Bulb strap for TE5 to TE55 delivered with the element
Danfoss A/S (AC-SMC / sw), 03 - 2011 DKRCC.PD.AB0.A3.02 / 520H5227
5
2
) ODF × ODM 3) ODM × ODM
ODF = Internal diameter ODM = External diameter
Ordering
(continued)
Evaporating temperature t e = +4.4°C Condensing temperature
t c = +38°C Refrigerant temperature ahead of valve
北京亚运会
开幕式t l =
+37°C
6 DKRCC.PD.AB0.A3.02 / 520H5227
李静轩
Danfoss A/S (AC-SMC / sw), 03 - 2011
Subcooling correction factor 'fsub'
Capacity in kW, range N, -40°C to +10°C, opening superheat sh= 4 K Q (capacity) = 45kW
Tcon (condensing temperature) = 25°C Tevap (evaporator temperature) = -30°C Tsub (subcooling temperature) =10K Dpd (distributer pressure drop) = 2 bar
Q (capacity) = 45kW
fsub (subcooling correction factor) = 1.09fp (distribution correction factor) = 0.85
Q = Selected capacity fsub x fp
45= 48.6 kW
1.09 x 0.85
The selection will be:
TE55 orifice 10 (52.70 kW > 48.6 kW)
How to select a valve:Example:湖图网