Operating time (years) General
Standards EN 55011, EN 55022, IEC/EN 61000−4, IEC 60068−2−6, IEC 60068−2−27
Dimensions (W × H × D)mm71.5 × 90 × 58 (4 PE) Weight kg0,2
Mounting Top−hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets
ZB4−101−GF1 (accessories)
Terminal capacities
Solid mm20.24 (AWG 22 – 12) Flexible with ferrule mm20.22.5 (AWG 22 – 12) Standard screwdriver mm 3.5 × 0.8
Max. tightening torque Nm0,6
Climatic environmental conditions
Operating ambient temperature°C −25 to 55, cold as per IEC 60068−2−1, heat as per IEC 60068−2−2板式换热器
选型 Condensation Take appropriate measures to prevent condensation
LCD display (clearly legible)°C055 Storage°C−40/+70 Relative humidity, non−condensing
(IEC/EN 60068−2−30)
% 5 – 95
Air pressure (operation)hPa795 – 1080 Corrosion resistance
IEC/EN 60068−2−42 4 days SO2cm3/m310
IEC/EN 60068−2−43 4 days H2S cm3/m31 Ambient conditions, mechanical
Pollution degree2
Degree of protection (IEC/EN
60529)
IP 20 Vibrations (IEC/EN 60068−2−6)
Constant amplitude 0.15 mm Hz10 – 57 Constant acceleration 2 g Hz57 – 150 Mechanical shock resistance
(IEC/EN 60068−2−27)
semi−sinusoidal 15 g/11 ms
Impacts18
2
Drop to IEC/EN 60068−2−31Drop height mm50
Free fall, packaged (IEC/EN
60068−2−32)
m1
Mounting position horizontal/vertical Electromagnetic compatibility (EMC)
Electrostatic discharge (IEC/EN
垃圾
打捞船
61000−4−2, Level 3, ESD)Air discharge kV8
Contact discharge kV6 Electromagnetic fields (IEC/EN
61000−4−3, RFI)
V/m10
Radio interference suppression (EN 55011)EN 55011 Class B, EN 55022 Class B
Burst pulses (IEC/EN 61000−4−4,
level 3)
Supply cables kV2 Signal lines kV2
High−energy pulses (surge) (IEC/EN 61000−4−5)kV
2 (supply cables,
symmetrical, AC)
High−energy pulses (surge) (IEC/EN 61000−4−5, level 2)kV
0.5 (supply cables,
symmetrical, DC)
Immunity to line−conducted
interference to (IEC/EN 61000−4−6)
V10 Insulation resistance
Clearance in air and creepage distances EN 50178, UL 508, CSA C22.2, no. 142封装外壳
Insulation resistance EN 50178
Backup/accuracy of the real−time clock
Accuracy of the real−time clock typ. ± 5 (± 0.5 hannually) Repetition accuracy of timing relays
Accuracy of timing relays (of values)%± 1
Resolution
Range “S”ms10
Range “M:S”s1
Range “H:M”min1
Retentive memory
Write cycles of the retentive memory1000000 (106)
Power supply
Rated operational voltage U e V12 DC (−15/+30%) Admissible range V DC10,2 – 15,6
Residual ripple% 5
3
Input current
Input current 115/230 V AC mA Normally 140
Voltage dips (IEC/EN 61131−2)ms10
Heat dissipation W Normally 2
vselDigital inputs 12 V DC
Number8
Inputs can be used as analog inputs 2 (I7, I8)
Status indication LCD−display (if present) Potential isolation
From power supply No
Between digital inputs No
汽水热交换器From the outputs Yes Rated operational voltage U e V DC12
On 0 signal U e V DC 4 (I1 – I8)
On 1 signal U e V DC8 (I1 – I8)
Input current on 1 signal
I1 to I6mA 3.3 (at 12 V DC)
I7, I8mA 1.1 (at 12 V DC)
Delay time from 0 to 1
Debounce ON ms20
Debounce OFF ms Normally 0.3 (I1 – I6), 0.35 (I7, I8)
Delay time from 1 to 0
Debounce ON ms20
Debounce OFF ms Normally 0.3 (I1 – I6), 0.15 (I7, I8)
Cable length (unscreened)m100 Frequency counter 2 (I3, I4) Fast counter inputs 2 (I1, I2) Max. counter frequency kHz< 1 Pulse shape Square Pulse pause ratio 1 : 1 Cable length screened m< 20 Analog inputs
Potential isolation
From power supply No From the digital inputs No From the outputs Yes
No
4
From the PC interface, memory card
NET network, EASY−Link
Input type DC voltage
Signal range V DC0 – 10 Resolution, analog V0,01 Resolution, digital V0,01 Resolution, digital Bit10 (value 1 – 1023) Input impedance k11,2
Accuracy of actual value
Two EASY devices%± 3
Within a single device%± 2, ± 0.12 V
Conversion time, analog/digital ms Debounce ON: 20; Debounce OFF: every cycle time
Input current mA< 1
Cable length screened m< 20
Relay outputs
Number4
Outputs in groups of1
Parallel switching of outputs for
increased output
Not permissible
Protection of an output relay Miniature circuit−breaker B16 or fuse 8 A (slow)
Potential isolation
From power supply Yes From the inputs Yes From the PC interface, memory card
NET network, EASY−Link
No Safe isolation V AC300 Basic insulation V AC600 Lifespan, mechanical Operations× 10610 Contacts碗形垫片
Conventional thermal current (10 A
UL)
A8 Recommended for load: 12 V
AC/DC
mA> 500 Short−circuit−proof cos = 1,
characteristic B16 at 600 A
A16 Short−circuit−proof cos = 0.5 to 0.7,
characteristic B16 at 900 A
A16 Rated impulse withstand voltage kV6
5