变压器技改方案

EXTERNAL NOTE
REF.: NE8181208
TO : Client FROM :    Service Engineering Dept. C/ : C/ :
Fecha: 31/08/2012
IMPROVEMENTS IN TRANSFORMER ROOM AND PROTECTIONS IN CHINA WF
中国风场关于变压器室及其保护的改进
INDEX 索引
1.OBJECT目标 (2)
2.DESCRIPTION OF THE IMPROVEMENTS 改善的描述 (2)
2.1.CHECKING TRANSFORMER DELTA RODS/检查变压器桥接母线 (2)
2.2.FOAM REMOVAL/泡沫去除 (2)
2.3.MV FLEXIBLE CONNECTION  MV柔性连接 (2)
茶子粉2.4.PROTECTION AGAINST HIGH VOLTAGE SWITCHGEAR UNCONTROLLED RECONNECTION防止高
压环网柜不受控重上电的保护 (3)
2.5.RELOCATION OF ARC SENSORS IN THE TRANSFORMER ROOM 在变压器室内弧光传感器移位 (3)
2.6.NEUTRAL BAR INSULATION /中线点母线排的绝缘 (3)
2.7.ALUMINUM BUS BAR  / 铝母线排加强 (4)
3.ACTION PLAN 行动计划 (5)
EXTERNAL NOTE
REF.: NE8181208
28/05/2012
1. OBJECT目标
The purpose of this External Note is to describe the improvements to be performed in the transformer room and transformer protections in G9X Wind Farms in China.
此文档的目的是描述中国G9X风场变压器室和变压器保护改善工作的实施。
2. DESCRIPTION OF THE IMPROVEMENTS 改善的描述
鞋帮The following sections describe the improvements to be performed.
下面内容是描述改善工作的实施。
2.1. CHECKING TRANSFORMER DELTA RODS/检查变压器桥接母线
The works consist of checking all the Delta rods of the transformers:
这项工作包括所有桥接母线的检查:
- Looking for deformed bars by repeated manipulations 仔细检查多次操作后有无异常变形
- Inspecting bars insulation 检查接线排的绝缘
- Verifying any damage on it or any overheating sign 确认任何的损坏或过热灼痕
- Verifying that junction zone between both ends of each bar is in perfect condition, with no deformation, cracks, overheating signs nor bolts without torque. 确认每个母线排两端
的连接处处于完好状态,无任何变形,开裂,灼痕,或者扭矩不正常。
If anything abnormal, replace the rods. 如果有异常,更换此桥接母线。
The latest model of Delta rods are installed in those transformers which do not have them.
装有最新型的桥接母线的变压器上面没有左图中的部件。
2.2. FOAM REMOVAL泡沫去除
Remove the foam in the transformer room.
去除变压器室的隔音绵。
柔性连接
2.3. MV FLEXIBLE CONNECTION  MV柔性连
错位匹配
The improvement consists of installing flexible connections between the transformer and the HV cable to avoid enforced positions that may damage the connection with the vibrations.
该技改包含在变压器和HV电缆间安装柔性连接,以避免因为震动而损坏连接部位。
EXTERNAL NOTE
REF.: NE8181208
28/05/2012
2.4. PROTECTION AGAINST HIGH VOLTAGE SWITCHGEAR UNCONTROLLED
RECONNECTION 防止高压环网柜不受控防止高压环网柜不受控重上电重上电重上电的保护的保护
电梯门机系统To improve the protection of the wind turbine a new set of locking relays is installed, with next purpose:
基于以下目的,为改善风机的保护功能,安装一套新的闭锁继电器的装置:
-
Avoid uncontrolled reconnection of HV switchgear until a deep check is carried out  避免HV 环网柜在得到进一步检查之前而不受控的重上电
-
Help the diagnosis in field to determine the origin of the disconnection  帮助现场人员判断当前断开连接的原因  2.5. RELOCATION OF ARC SENSORS IN THE TRANSFORMER ROOM 在变压器室内弧
光传感器移位
The transformer room is currently protected with two arc detectors installed on the wall separating the transformer area from the rest of the turbine, just in front of the HV bus bar.  目前变压器室由两个安装在变压器墙面上的弧光传感器保护,就在HV 母线排前面。
金属粉末涂料The detectors act through photovoltaic sensors, whose relay, on detecting an electrical arc, sends a rapid system cut-off pulse.
该元件是通过弧光传感器动作,当发现电弧光时其继电器向系统发出一个迅速切断脉冲的信号。
The protection for the rear area between the transformer and the nacelle wall (low voltage of the transformer) is improved by moving one of the existing sensors to this area.
癸氧喹酯后部的保护,即变压器和机舱墙壁间(变压器低压),通过移动其中一个传感器来改善。
2.6. NEUTRAL BAR INSULATION /中线点中线点母线母线母线排排的绝缘
To eliminate the risk of short circuit between phase and neutral bus bar in case a bar is broken, an extra insulator is installed.
为了消除因某一接线排损坏而造成相线和中性线母线排间短路的危险,加一个额外的绝缘体。 It will be installed on the neutral bus bar, as a cap, at the closest point to phase bars.
它将被安装在中性点母线排,在最靠近相线母线的位置。
EXTERNAL NOTE
REF.: NE8181208
28/05/2012
2.7. ALUMINUM BUS BAR  / 铝母线
排加强
铝母线排
The improvement consists of reinforcing Fuses bar support to reduce bus bar stress in phase C.
Replacement of the transformer L support by a reinforced one, route the cables between the cables support and the fuse cooper plate in a curve way and fuse cooper plate is replaced in order to allow the new cables routing.
该技改包括加强保险接线排支撑,以便减少C相母线排的压力。把变压器L形支撑更换成加强型,在电缆支撑和保险铜排之间的布线有一个弧度,为使新的电缆布线更合理,保险铜排将被更换。
In addition rubber blocks of the wires fixing brackets are checked, verifying that they are in good condition, the absence of cracks, deformation or any clearance. Replacement of the phase W cables supports
除此之外,电缆固定支架的橡胶块也需要检查,以确保状态完好,没有裂纹、变形及空隙。并更换W相的电缆支撑。
EXTERNAL NOTE
REF.: NE8181208
28/05/2012
计划
3. ACTION PLAN实施
实施计划
Above design modification will be divided to 2 packages as follows上述技改分为如下2个技改包,
•Package 1: including 2.1 to 2.5, it will start in 2 week and finish in 4-5 weeks in each wind farm by 1 teams.
技改包1:包括2.1-2.5项,将在2周内开始实施, 每个风场1 组队伍,预计4-5周完
成。
•Package 2: including 2.6-2.7 will start later due to the limit of material production capability.
技改包2:包括2.6-2.7项,因为物料产能原因,将在晚些时候开始实施。