In 1.5, 2.5, 4, line 6, 10mm2 will be its cross-sectional area
multiplied by 5 times. In 16, 25mm2 wire can be multiplied by
4 times the cross-sectional area. In 35, 50mm2 wire can be
multiplied by 3 times the cross-sectional area. In 70, 95mm2
wire can be multiplied by 2.5 times the cross-sectional area.
For wire 120, 150 and 185mm2 to its cross-sectional area
multiplied by 2 times
The working temperature of 30 DEG C, 90% load under long-term
continuous flow is as follows: 1.5 mm - 18A2.5 mm - 26A4 mm -
26A6 mm - 47A10 mm - 66A16 mm - 92A 25 mm - 35 mm 120A - 150A
power P= voltage U * current I = 220 V * 18 = 3960 watt
GB4706.1-1992/1998 standard safety regulations of the wire
load current value (in part): copper wire. Copper wire
cross-sectional area. Allow long-term current..2.5 mm (16A ~
25A), 4 mm (25A ~ 32A)..6 mm (32A ~ 40A) aluminum core wire.
The aluminum core wire cross-sectional area. Allow long-term
current..2.5 mm (13A ~ 20A) 4 mm (20A ~ 25A), 6 mm (25A ~ 32A)
For example: ////1, / / / each computer power consumption is
about 200 ~ 300W (1 ~ 1.5A), then the 10 computer requires a
2.5 mm copper wire power supply, otherwise may cause fire. 2,
3 air-conditioning power consumption of about 3000W (about 14A),
then 1 air conditioners you need to separate a 2.5 square mm
copper wire power supply. 3, now housing into the line is
generally 4 square mm copper cable, therefore, at the same time
open the household appliances shall not exceed 25A (5500 watts),
it will be housing the wires replaced 6 square mm copper cable
is useless, because the wire into the meter is 4 square
millimeter. 4, early housing (15 years ago) into the line is
generally 2.5 square millimeters of aluminum, therefore, at the
same time open the household appliances shall not exceed 13A
(2800 watts). 5 household appliances, power consumption is
relatively large: air conditioning 5A (1.2 HP), electric water
heater 10A, 4A microwave oven, electric cooker 4A, dishwasher
8A, 10A washing machine with drying function, electric boiling
water heater 4A in power caused by the fire, 90% is the joint
caused by fever, therefore all the joints are to be welded, no
welding contactor 5 ~ 10 years must be replaced (such as air
switch socket, etc.)................ The long-term current GB
allows 4 square 25-32A6 square
In fact, these are the theory of safety value is greater than
the limit value, the maximum power 2,5 square wire allows the
use of 5500W. is 4 square 8000W square, 6 9000W no problem.40A
digital meter normal 9000W is absolutely no problem. The
mechanical 12000W will not be burned. 00 copper core cable
ampacity standard cable ampacity lips: estimation formula: two
point five multiplied by nine, to go up by a smooth number.
Thirty-five by three point five, both in groups by five points.
The conditions have changed with the conversion, the high
temperature of ten percent off copper upgrade. Intubation root
number two three four, 87 forty percent off full flow.
Note: this section formulas for various insulated wire (rubber
and plastic insulated wire) ampacity (safe current) is not
directly pointed out, "but the section multiplied by a certain
multiple" to that obtained by mental arithmetic. "Two point
five times nine, to go up by a smooth number" is 2.5mm "and
following the various cross-section aluminum insulated line,
its carrying capacity is about 9 times the number of cross
section. Such as 2.5mm 'wire carrying capacity for 2.5 x 9 =
22.5 (A). From the load flow and section number 4mm 'and above
lead multiple relationship is along the line to reach multiple
successive reduction L, 4 x 8, 6 x 7, 10 x 6, 16 x 5, 25 x 4.
"Thirty-five times three point five, both in groups by five,
3.5 times the conductor said is 35mm" carrying capacity for the
section number, that is 35 x 3.5 = 122.5 (A). From the 50mm 'and
above the wire between the carrying capacity and section number
multiple relationship into two two line into a group, followed
by a multiple of minus 0.5. 50, 70mm wire carrying capacity for
the section number 3 times; 95, 120mm wire carrying capacity
is 2.5 times the cross-sectional area of the number, and so on.
"Conditions plus the change in conversion, the high temperature
of ten percent off copper upgrade". The above formula is
aluminum core insulation wire, deposited in the environmental
temperature of 25 DEG C under the condition of the. If the
aluminum core insulation wire surface at ambient temperature
higher than 25 DEG C long area, the ampacity calculation method
can be calculated according to the formula, and then call ten
percent off to use but not the wire; when the copper core
insulation wire, to be slightly larger than the same size of
aluminum and its carrying capacity, can be calculated according
to the above formula method than the wire carrying a line to
increase the flow. If the flow load 16mm 'copper wire, according
to the calculation of aluminum 25mm2. The calculation of cable
ampacity of cable selection (according to the current selection
of cable): wire ampacities and wire section, or material type
and wire laying method and environmental temperature and so on,
there are many factors affecting the complicated calculation.
The carrying capacity of various wire can usually be found in
the manuals. But the use of formulas with some simple arithmetic,
can be calculated directly, without look-up table. 1. formulas
of aluminum core insulation wire carrying capacity and section
10 under five multiples of 100, two, 25, 35, four, three,.70,
95, two and a half times. Through pipe, temperature, eight or
nine fold. Add half bare. Copper is upgrade.
Description formulas for various section carrying capacity
(ANN) is not directly pointed out, but with the section
multiplied by a certain multiple representation. This will be
our common wire nominal section (mm2) are arranged as follows:
1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150,
(1) pointed out that the first sentence rhymes aluminum core
insulated wire carrying capacity (ANN), according to the times
of calculation section. The formulas in Arabia digital said the
conductor section (mm2), Chinese characters digital times. The
formulas of section and multiple relationships arranged as
follows: 1 to 1016, 2535, 5070, 95120 > > > > > five times four
times three times two times two times now and then control
formulas more clearly, as "10 under five" refers to the section
below 10, carrying capacity is five the number of times the
value of the cross section.
"100 two" (read 100 two) refers to the section of ampacity is
two times more than 100 section numerical. Section 25 and 35
is the boundary between the four and three times. This is the
formula 25, 35, four realms "". While section 70, 95 to two point
five times. From the above arrangement can be seen: in addition
to below 10 and 100 above, the wire section is in the middle
of each of the two specifications are of the same kind of
multiples. For example, aluminum core insulation wire,
temperature ampacity calculation is not greater than 25 DEG C:
when the section is 6 mm, as load flow is 30; when the section
is 150 mm, as load flow is 300; when the section is 70 mm, is
the carrying capacity for the 175. From the above arrangement;
also can be seen: with the cross-section ratio increases, at
the junction of multiple changes, the error is slightly larger.
For example, section 25 and 35 is the boundary between the four
and three times, four times the range of 25 genera, which
according to the formula for the 100 count, but according to
the manual for the 97 and 35; instead, according to the formula
is 105, but the look-up table for the 117. But this did not
affect the use of. Of course, if a few chest, in the lead section,
25 do not make it full to 100, 35 is slightly more than 105.
It is more accurate. Also, the location of the line 2.5 square
mm five times in the beginning, in fact more than five times
(maximum 20 above), but in order to reduce the power loss in
the wire, usually are not so much to the current manual, only
12. (2) three is behind the formulas for processing conditions
change. "Wear tube, temperature, eight or nine fold" means: if
the laying (including groove plate, wire laying is a protective
sleeve layer, exposed, after calculating the unknown), call
twenty percent off; if the ambient temperature is above 25
degrees Celsius, then play the ten percent off calculation, if
both laying, and temperature more than 25 DEG C, call ten
percent off call twenty percent off, or by a simple thirty
percent off computing. About the environmental temperature,
according to the Regulations refers to the highest average on
the hottest summer temperatures. In fact, the temperature
change is, in general, it is not a large current carrying
conductor. Therefore, only for some warm or hot workshop area
more than 25 degrees more, before considering a discount. For
example, aluminum insulated line in different conditions
calculated download traffic: when the cross section is 10 mm
in the tube, then load flow is 10 x 5 x 0.8 40 one; if the
temperature is loaded flow is 10 x 5 x 0.9 45 one; if the pipe
and high temperature, then load flow 10 x 5 x 0.7 one 35. (3)
for the traffic load of bare wire, pointed out that "bare plus
half" formula is calculated after the half. This refers to the
same section of bare aluminum and aluminum core insulation wire,
can increase the carrying capacity of half.
For example, the calculation of ampacity of bare wire: when the
section is 16 mm, while the load flow is 16 x 4 x 1.5 one 96,
if under high temperature, then load flow is 16 x 4 x 1.5 x
0.9=86.4. (4) for the current carrying capacity of copper wire,
copper is pointed out that the formula upgrade ", is about to
cross section copper wire sequence level, and then calculate
the corresponding condition of aluminum. For example, section
35 square mm bare copper wire environment temperature is 25 DEG
C, ampacity calculation is: according to the upgrade to 50
square millimeter of bare wire is 50 x 3 x 1.5=225. For cable,
not introduced in the formula.
High voltage cable directly buried, it can be directly used for
the calculation of multiple first formulas. For example,
current carrying capacity of 35 square mm high-pressure steel
clad aluminum core cable buried for 35 * 3=105. 95 mm is about
95 * 2.5 = 238. The zero line of the three-phase four wire system
in cross section, usually selected as the phase section of about
1/2. Of course not less than the minimum allowable section
according to the requirement of mechanical strength. In
single-phase circuit, due to the load current through the zero
line and the line of the same, so the zero line cross section
should be the same as the phase section. The type name of the
scope of application of YJV copper core PE insulated PVC
sheathed power cable for laying indoors, in tunnel and in the
pipeline, the cable can not bear the pressure and mechanical
force. VLV YJV22 aluminum core copper conductor XLPE insulated
steel tape armored PE sheathed power cable for laying indoors,
in tunnel and cable buried in the soil, can withstand the
pressure and other external force. VLV22 VV32 PVC insulated
steel wire armoured PVC sheathed power cable for laying indoors,
in mine cable can withstand considerable tension. VLV32 VV42
PVC insulated steel wire armoured PVC sheathed power cable for
laying indoors, in a mine, the cable can withstand considerable
axial tension. VLV42 ZR-VV PVC insulated PVC sheathed flame
retardant power cable for laying indoors, in tunnel and in the
pipeline, the cable can not bear the pressure and mechanical
force. ZR-VLV ZR-VV22 PVC insulated PVC sheathed flame
retardant power cable for laying indoors, in tunnel and cable
buried in the soil, can withstand the pressure and other
external force. ZR-VLV22 ZR-VV32 PVC insulated fine steel wire
armored PVC sheathed flame retardant power cable for laying
indoors, in mine cable can withstand considerable tension.
ZR-VLV32 ZR-VV42 PVC insulated steel wire armoured PVC sheathed
flame retardant power cable for laying indoors, in a mine, the
cable can withstand considerable axial tension. ZR-VLV42 type
of cable is composed of eight parts: first, use the code - not
for power cable, control cable for K, P for signal cable; two,
insulation code Z paper, X rubber, V PVC, YJ cross-linked
polyethylene three, conductor material code standard for
copper, aluminum L; four, the internal layer of code - Q lead
package, L aluminum clad, H rubber, V PVC sheath five, D code
derived no dropping, P dry insulation; six, outer layer code
seven, special product code TH TA dry wet tropical, tropical;
Eight, rated voltage unit KV cable type SYWV (Y) SYKV, cable
TV, broadband network cable structure: (coaxial cable)
anaerobic single round copper wire + physical foaming
polyethylene (insulation) + (tin wire + Al) + PVC (PE), 2 signal
control cable (RVV cable, RVVP shielded wire) applicable to
building intercom, burglar alarm, fire control, automatic
meter reading engineering 3, RVVP copper conductor PVC
insulated PVC sheathed shielded flexible cable voltage
300V/300V 2-24 core use: instrument, intercom, monitor and
control the installation of KVVP: 4, PVC sheathed braided
shielding cable use: electrical appliances, instrumentation,
power distribution equipment signal transmission, control,
measurement, 5 RVV (227IEC52/53) PVC insulated flexible cable
use: household appliances, small Electric tools,
instrumentation and power lighting, 6 RV, 7 RVS, PVC insulated
cable is suitable for connecting RVB small household electrical
appliances, electric tools, instruments, meters and power
lighting cable 8, BV, BVR PVC insulated cables use: used in
electrical equipment and power meter, according to the 9 KVV
PVC insulated control cable used in Ming Dynasty fixed wiring:
electrical appliances, instrumentation, power distribution
equipment, signal transmission, control and measurement of RVV
KVV RVVP and KVVP RVV and RVVP difference: inside the line for
multi strand thin copper wire composed of cords composed of RV
line. KVV and KVVP inside the line for the hard line single
strand copper composition, composition of BV line. AVVR and
RVVP: difference between things, just name internal section
less than 0.75 mm for AVVR greater than 0.75 mm is equal to the
name of RVVP. SYV SYWV and the difference is: SYV video
transmission line with polyethylene insulation. SYWV is the RF
transmission line, physical foaming insulation. Used for cable
television. RVS and RVV 2 core difference: RVS dual core RV wire
twisted, no outer sheath, for radio connection. RVV 2 core cable
repeater, a sheath, used in power supply control signal R is
connected by a flexible cable (wire), soft structure. V - PVC
insulation. V - PVC insulated PVC sheathed flat - V (flat). S
twisted pair. A tin or silver plated. F high temperature
resistant P P2 copper shielded braid shield P22 - Y - type
prefabricated steel tape armoured, generally omitted, or FD -
polyolefin sheathed category code, a branch cable. The Ministry
of construction standards will be issued by FZ, in the same YJ
XLPE insulated PVC insulation or sheath of V - ZR - NH - type
flame retardant refractory WDZ halogen-free flame retardant
WDN low smoke halogen-free fireproof
本文发布于:2024-09-24 12:29:37,感谢您对本站的认可!
本文链接:https://www.17tex.com/fanyi/1375.html
版权声明:本站内容均来自互联网,仅供演示用,请勿用于商业和其他非法用途。如果侵犯了您的权益请与我们联系,我们将在24小时内删除。
留言与评论(共有 0 条评论) |